IFM SA4100 Flow Sensor — calorimetric flow + temperature with red/green display, Ø8 mm clamp, 100 mm probe, 50 bar, analog + IO-Link. calorimetric flow and temperature sensor for water, oils and air, Ø8 mm clamp fitting with 100 mm probe, 50 bar rated, red/green display, 2 switching outputs plus analog 4...20 mA and IO-Link, IP65/IP67.
Shipping & Returns
Same-day dispatch across UAE
Order before 2 PM (Sun–Thu). Next-day delivery to Dubai, Sharjah, Abu Dhabi. 2–4 days to other emirates.
7-day return window
Sealed, unused items can be returned within 7 days for full refund or replacement.
Compatibility-checked
Our specialists review every bulk quote to ensure the part fits your application before you commit.
MPN / SKU: SA4100
Also known as: IFM SA4100 flow switch / flow meter / flow monitor.
SA4100 Applications
The IFM SA4100 flow sensor measures flow velocity and medium temperature simultaneously in water, glycol, oil and air lines, with a long 100 mm probe for larger pipes via a Ø8 mm clamp fitting. Its red/green display, analog output and IO-Link suit cooling-circuit and lubrication monitoring and pump protection in demanding industrial plant.
The SA4100 measures liquids at 0.04...6 m/s (relative) or 0.04...3 m/s (absolute), and gases at 2...200 m/s (relative) or 2...100 m/s (absolute).
What measuring principle and media does the SA4100 use?
The SA4100 uses the calorimetric measuring principle for media including water, glycol solutions, air, and oils.
What is the accuracy and response time of the SA4100?
The SA4100 has a relative-mode accuracy of +/-(7 percent of MW + 2 percent of MEW), absolute-mode repeatability of 0.05 m/s, and a response time of 0.5 s (water/glycol 0.8 s, air 7 s, oil 1.8 s).
What outputs and IO-Link does the SA4100 provide?
The SA4100 has 2 digital outputs and 1 analogue output (4...20 mA, scalable, max load 350 Ohm), with a permanent current rating of 250 mA, plus IO-Link revision 1.1 at COM2 (38.4 kBaud).
What temperature ranges does the SA4100 support?
The SA4100 handles a medium temperature of -20...100 degrees C (also its measurement range) and an ambient temperature of -40...80 degrees C.
What is the operating voltage, materials, and pressure rating of the SA4100?
The SA4100 operates on 18...30 V DC, draws less than 100 mA, uses stainless steel (316L/1.4404) housing and wetted parts, and is rated to 50 bar (5 MPa).
What is the process connection and protection rating of the SA4100?
The SA4100 uses a clamp adapter Ø 8 mm process connection and is rated IP 65 and IP 67.
Does the SA4100 measure temperature and have a display?
Yes, the SA4100 monitors temperature alongside flow and has a red/green 4-digit alphanumeric display with 6 LEDs.
Being a UAE company, our UAE shipments are subject to tariffs. Under DDP (Delivered Duty Paid), all applicable tariffs and fees are calculated and paid upfront at checkout.
Same-day dispatch across UAE
Order before 2 PM (Sun–Thu). Next-day delivery to Dubai, Sharjah, Abu Dhabi. 2–4 days to other emirates.
7-day return window
Sealed, unused items can be returned within 7 days for full refund or replacement.
Compatibility-checked
Our specialists review every bulk quote to ensure the part fits your application before you commit.