IFM AC009S - AS-Interface Safety Module, 2 Safe Inputs, SIL3 Relay

IFM AC009S - AS-Interface Safety Module, 2 Safe Inputs, SIL3 Relay

SKUAC009SBrandIFM
Regular price AED 946.11
Regular price AED 1,051.25 Sale price AED 946.11
Sale Sold out
Shipping calculated at checkout.

Only 6 left

IFM AC009S AS-Interface Safety Module — AS-i SmartLine safety module, 2 safe inputs + 2 relay outputs, SIL3 / PLe, DIN-rail. AS-Interface safety module, 2 safe inputs (cross-monitored) + 2 relay outputs, SIL3 / ISO 13849 PLe, DIN-rail, 26.5...31.6 V DC, IP20.

Shipping & Returns

Same-day dispatch across UAE

Order before 2 PM (Sun–Thu). Next-day delivery to Dubai, Sharjah, Abu Dhabi. 2–4 days to other emirates.

7-day return window

Sealed, unused items can be returned within 7 days for full refund or replacement.

Compatibility-checked

Our specialists review every bulk quote to ensure the part fits your application before you commit.

MPN / SKU: AC009S

AC009S Applications

The IFM AC009S is an AS-Interface control cabinet safety module used to connect mechanical safety switches to an AS-i safety network. It is suited for E-stop, guard-door and interlock monitoring on machines using AS-i Safety at Work. It provides two safe inputs with cross-monitoring and two relay outputs, meets ISO 13849-1 Category 4 PLe and IEC 61508 SIL3, and uses powerful LEDs to show operation, switching status and errors. The space-saving DIN-rail housing wires quickly via screw terminals.

AC009S Specifications

Brand IFM Product Type AS-Interface control cabinet safety module
IFM Type Code SmartLine SafetyModul Inputs 2 x safe input (PNP, cross-monitored)
Outputs 2 x relay (24 V DC / 10...240 V AC, 6 A ohmic) Safety Rating SIL3 (IEC 61508); Cat 4 PLe (ISO 13849-1)
PFH 4E-09 /h AS-i Profile S-7.B.E; AS-i v2.11 / 3.0
Operating Voltage 26.5...31.6 V DC (AS-i) Mounting DIN rail TH35 (EN 60715)
Dimensions 93 x 25.4 x 108 mm Protection Rating IP 20
Ambient Temperature -25...50 °C Housing Material PC-GF20
Electrical Connection Screw terminals / pin headers Weight 258 g

AC009S – Frequently Asked Questions (FAQ)

How many safe inputs does the IFM AC009S have?

It has 2 digital safety inputs with PNP DC circuit configuration and a total current rating of 100 mA.

What safety rating does the AC009S meet?

It meets ISO 13849-1 category 4, PL e and IEC 61508 SIL 3, with a mission time of 20 years.

What relay outputs does the AC009S provide?

It has 2 relay outputs rated at a maximum of 6000 mA each, capable of DC (24 V) or AC (10-240 V) switching; outputs must be paired with identical voltage supply.

What AS-Interface profile and addressing does the AC009S use?

It supports AS-i version 2.11 / 3.0 with profile S-7.B.E, uses an addressing socket, and carries AS-i certificate 62001.

What operating voltage and current does the IFM AC009S need?

It operates on 26.5...31.6 V DC, drawing a maximum of 250 mA from AS-i, with a total load capacity of 6 A.

What is the housing material, IP rating and mounting of the AC009S?

The housing is PC-GF20, rated IP 20, in a rectangular design for DIN-rail mounting (TH35, EN 60715).

What is the operating temperature of the AC009S?

The ambient operating temperature range is -25...50 deg C.

What diagnostic features does the IFM AC009S offer?

It has an integrated watchdog and electrically separated outputs, with LED status indicators for switching, operation and errors.

View full details

Same-day dispatch across UAE

Order before 2 PM (Sun–Thu). Next-day delivery to Dubai, Sharjah, Abu Dhabi. 2–4 days to other emirates.

7-day return window

Sealed, unused items can be returned within 7 days for full refund or replacement.

Compatibility-checked

Our specialists review every bulk quote to ensure the part fits your application before you commit.