- Brand
- Sick
- Pressure Reading Type
- Compound Pressure
- Minimum Pressure Reading
- -0.16 bar
- Maximum Pressure Reading
- -0.16 bar ... 0 bar
- Accuracy
- ≤ ± 0.5 %, of the span (= ± 0.25% of the span (optionally for pressure ranges = 0.25 bar). applies inclusive of nonlinearity, hysteresis, non-repeatability, zero-point and full-scale error (corresponds to error of measurement as per IEC 61298-2) Calibrated with vertical installation position)
- Output Type
- Analogue
- Media Measured
- Liquid, gaseous
- Process Connection
- G ¼ A (ISO1179-2)
- Analogue Output
- 4 mA ... 20 mA, 2-wire (RA ≤ (L+ – 10 V) / 0.02 A [Ohm]) , 0 V ... 5 V, 3-wire (RA > 5 kOhm), 0 V ... 10 V, 3-wire (RA > 10 kOhm)
- Electrical Connection
- M12 round connector x 1, 4-pin
- Response Time
- ≤ 1 ms ≤ 10 ms at medium temperatures below < -30°C for pressure ranges up to 25 bar or with flush-mounted membrane
- Series
- PFT
- Supply Voltage
- 10 V DC ... 30 V DC
- Housing Material
- Stainless Steel 1.4571
- Standards/Approvals
- Pressure equipment directive: 2014/68/EUEMC directive: 2004/108/EC, EN 61326-2-3
- Minimum Operating Temperature
- -40 °C
- Maximum Operating Temperature
- 80 °C
- IP Rating
- IP67
Being a UAE company, our UAE shipments are subject to tariffs. Under DDP (Delivered Duty Paid), all applicable tariffs and fees are calculated and paid upfront at checkout.
Same-day dispatch across UAE
Order before 2 PM (Sun–Thu). Next-day delivery to Dubai, Sharjah, Abu Dhabi. 2–4 days to other emirates.
7-day return window
Sealed, unused items can be returned within 7 days for full refund or replacement.
Compatibility-checked
Our specialists review every bulk quote to ensure the part fits your application before you commit.